Your location:



The H12 Vertical Liquid Cooling Check Valve is an automatic valve designed specifically for data center liquid cooling cabinets, cooling tower circulation systems, and compact liquid cooling pipelines. Utilizing a vertical lift structure, the valve opens automatically under medium pressure and closes via the disc’s weight and backflow. For liquid cooling applications, the body is precision-cast from high-grade stainless steel with a hydrodynamically optimized disc, ensuring sensitive operation even in low-pressure differential environments to prevent backflow damage to pumps and precision electronics.

Product Image:H12 Vertical Liquid Cooling Check Valve
Feature
1、Vertical Guided Structure: The unique vertical lift design ensures the disc moves smoothly along the guides for accurate resetting during closure.
2、Ultra-Low Cracking Pressure: Optimized disc weight for low-pressure cooling loops ensures rapid opening upon pump startup, reducing system energy consumption.
3、Dead-Zone Free Cavity: Smooth internal surfaces prevent sediment accumulation, compatible with deionized water and glycols to maintain system cleanliness.
4、Compact Threaded Connection: Standard female threads allow for a small footprint, ideal for space-constrained cooling modules or Cooling Distribution Units (CDU).
5、Quiet Closure Design: Precision-ground disc and seat (with optional soft seals) effectively absorb vibration and noise, suitable for quiet office or server room environments.
6、Corrosion-Resistant & Durable: All-stainless steel construction withstands frequent thermal cycling and prevents ion contamination, extending the maintenance cycle.

Structure Diagram:H12 Vertical Liquid Cooling Check Valve
Material List
| No. | Parts | Material |
| 1 | Body | CF8 / CF8M |
| 2 | Disc | CF8 / CF8M |
| 3 | Spring | 304 / 316 |
| 4 | Gasket | PTFE |
| 5 | Bonnet | CF8 / CF8M |
Performance Specification Sheet
| Performance Specification Sheet | ||||
| Nominal Pressure | 1.0 | 1.6 | 2.5 | MPa |
| Strength test pressure | 1.5 | 2.4 | 3.8 | |
| Sealing test pressure | 1.1 | 1.76 | 2.8 | |
| Applicable Temperature | -40~180 | ℃ | ||
Standard requirements for external dimensions
Product approved by PED97/23/EC (CE0036)
Casting approved by AD2000-W0
Thread conforms to: ASME B1.20.1, BS21.0, DIN2999/259, ISO228-1, JIS B 0203, ISO7/1
Inspection & Testing: API598, EN12266

Outline Drawing:H12 Vertical Liquid Cooling Check Valve
Outline Dimension Table (Unit:mm)
| Size | Nominal Diameter | d | L | D |
| 1/4" | DN6 | 10 | 52 | 32 |
| 3/8" | DN10 | 12 | 52 | 32 |
| 1/2" | DN15 | 14 | 60 | 35 |
| 3/4" | DN20 | 19 | 69 | 40 |
| 1" | DN25 | 24 | 80 | 46.5 |
| 1-1/4" | DN32 | 31 | 87 | 56 |
| 1-1/2" | DN40 | 38 | 100 | 67 |
| 2" | DN50 | 49 | 119 | 80.5 |

Model:
YH76-10P/YH76-16P/YH76-25P/YH76-10R/YH76-16R/YH76-25RSpecification:
DN50-DN1200Pressure:
PN10~25Material:
Deionized water, Ethylene glycol, Propylene glycol solution, Mineral oil, Synthetic oil, Silicone oil, Perfluoropolyether (PFPE), Hydrofluoroether (HFE)
Model:
YD41X-10P/YD41X-10R/YD41X-16P/YD41X-16RSpecification:
DN50-DN2400Pressure:
PN10~16Material:
CF8,CF8M
Model:
YQ684F-10P/YQ684F-10R/YQ684F-16P/YQ684F-16RSpecification:
DN20-DN100Pressure:
PN10~16Material:
CF8,CF8M