Your location:



The air foam maker is a fixed foam fire extinguishing device installed on storage tanks or oil pools. It draws in air and thoroughly mixes the foam concentrate solution with air to produce a certain expansion ratio of air foam, which is then discharged onto the burning liquid surface to achieve extinguishment by coverage. Its core purpose is to provide low or medium expansion foam fire protection for flammable liquid storage tanks (such as crude oil, gasoline, alcohols, chemical solvents, etc.) . During a fire, it rapidly generates a large volume of foam to cut off oxygen, suppress vaporization, cool the surface, prevent fire spread, and effectively extinguish tank fires.

Product Drawing of Air foam generator
Features:
1. Simple structure and convenient installation: It is composed of shell, foam nozzle, air intake and mixing chamber. It is connected by flange and can be directly installed on the top or side wall of the tank.
2. High mixing efficiency: the foam mixture is fully mixed with air using the venturi principle, and the foam foaming ratio is stable (usually 3-8 times for low multiples and 20-40 times for medium multiples).
3. Fast fire extinguishing and uniform coverage: the generated foam has good fluidity and can quickly spread the burning surface to form a continuous covering layer to isolate oxygen and inhibit re combustion.
4. Corrosion resistant material: The shell and internal components are made of stainless steel (304/316) or copper alloy, which is resistant to corrosive media inside the storage tank and outdoor environments.
5. Linkage with fire control system: it can be linked with foam proportioning device, fire pump and pipe network, and automatically or manually start liquid supply in case of fire.
6. Suitable for various foam solutions: suitable for protein foam, fluoroprotein foam, aqueous film forming foam (AFFF) and other foam extinguishing agents.
7. Easy maintenance: Regularly check if the air intake is blocked and clean the internal dirt to restore performance.
8. Comply with the fire code: the design and manufacture shall comply with the standards such as General Technical Conditions for foam Fire Extinguishing Systems and Components (GB 20031).

Structure Diagram of Air foam generator
part name
| 序号 | 零件名称 / English Name | 材质 / Material |
| 1 | 密封玻璃 Sealing Glass | 钢化夹层玻璃 Tempered scored glass |
| 2 | 玻璃压圈 Glass Retainer Ring | HT200 灰铸铁 / 304 不锈钢 HT200 cast iron /304 stainless steel |
| 3 | 喷嘴 Nozzle | ZL104 铸铝 / 304 不锈钢 ZL104 cast aluminum /304 stainless steel |
| 4 | 进气滤网 Air Inlet Screen | 304 网 + Q235 框架 304 mesh + Q235 carbon steel frame |
| 5 | 弧形防护罩 Arc Cover | Q235 碳钢喷环氧 Epoxy coated Q235 steel |
| 6 | 主体壳体 Main Body | WCB/HT200/304 不锈钢 WCB/HT200/304 stainless steel |
| 7 | 泡沫输出管 Foam Outlet Pipe | Q235 焊管 / 304 无缝管 Q235 welded pipe/304 seamless pipe |
| 8 | 连接法兰 Connecting Flange | 同壳体材质 Same as body material |
| 9 | 导流板 Deflector Plate | 冲压 Q235 钢板 Stamped Q235 steel |
Performance Specification Table
| 参数名称 / English | PC4 | PC8 | PC16 | PC24 |
| 型号Model | PC4 | PC8 | PC16 | PC24 |
| 额定压力MPa Rated Pressure | 0.5 | 0.5 | 0.5 | 0.5 |
| 工作压力区间MPa Working Pressure | 0.4~0.6 | 0.4~0.6 | 0.4~0.6 | 0.4~0.6 |
| 额定流量L/s Rated flow | 4 | 8 | 16 | 24 |
| 发泡倍数 Foam ratio | ≥6 | ≥6 | ≥6 | ≥6 |

Model:
HX5-16/HX5-25/HX5-16P/HX5-25P/HXF5-16/HXF5-25/HXF5-16P/HXF5-25PSpecification:
DN50~DN500Pressure:
1.6MPa~2.5MPaMaterial:
cast iron, aluminum alloy, stainless steel
Model:
XYXA-500C/XYXA-600C/XYXA-500P/XYXA-600PSpecification:
DN500-DN600Pressure:
0.6Mpa -2.0MpaMaterial:
cast steel, stainless steel
Model:
HGS07-25/HGS07-25/HGS07-25C/HGS07-40C/HGS07-25P/HGS07-40PSpecification:
DN50-DN250Pressure:
0.6~6.4MPaMaterial:
cast iron, cast steel, stainless steel